Bell & Gossett 10 001 265R5 TechnoForce Pump Controller User Manual
Page 44

TECHNOFORCE Installation, Operation, and Maintenance
38
4.10.47 High level
Paths: Status Screens / Set up(3) / AlrmEvt(5) / High Level(8)
The High Level menu is displayed below:
High Level Time: ###s
Stop Pumps?: $(Y/N)
Auto Reset?: $(Y/N)
OK? $ (Y/N)
See following table for all
HIGH LEVEL menu items.
High level Menu Items
Menu Item
Variable
Default Range Field
Value
High Level
High Level Time: ###s
0
0-999
The proof time, in seconds prior to setting a high level
event, see section 4.10.17 to set up the high level digital
input. A value of 0 in High Level Time variable disables
the High Level function.
Stop Pumps?: $(Y/N)
N
Y/N
Select “Y” to allow pumps in this event to be
automatically stopped.
Auto Reset?: $(Y/N)
N
Y/N
Select “Y” to allow this event to be automatically reset.
4.10.48 VFD/Comm Failure
Paths: Status Screens / Set up(3) / AlrmEvt(5) / VFD Comm(9)
The
VFD/Comm Failure menu is displayed below:
VFD Proof Time: ###s
VFD COMM Pr Tm: ###s
OK: $(Y/N)
See following table for all
VFD/COMM FAILURE menu items.
VFD/Comm Failure Menu Items
Menu Item
Variable
Default Range Field
Value
VFD
VFD Proof Time: ###s
30
30-999
Comm
The proof timer prior to setting the VFD fail
Failure
alarm, in seconds.
VFD COMM Pr Tm: ###s
30
30-999
The proof timer prior to setting the VFD
communication fail alarm, in seconds.