TECHNOFORCE Installation, Operation, and Maintenance

38

4.10.47 High level

Paths: Status Screens / Set up(3) / AlrmEvt(5) / High Level(8)
The High Level menu is displayed below:
High Level Time: ###s
Stop Pumps?: $(Y/N)
Auto Reset?: $(Y/N)
OK? $ (Y/N)
See following table for all

HIGH LEVEL menu items.

High level Menu Items

Menu Item

Variable

Default Range Field

Value

High Level

High Level Time: ###s

0

0-999

The proof time, in seconds prior to setting a high level

event, see section 4.10.17 to set up the high level digital

input. A value of 0 in High Level Time variable disables

the High Level function.

Stop Pumps?: $(Y/N)

N

Y/N

Select “Y” to allow pumps in this event to be

automatically stopped.

Auto Reset?: $(Y/N)

N

Y/N

Select “Y” to allow this event to be automatically reset.

4.10.48 VFD/Comm Failure

Paths: Status Screens / Set up(3) / AlrmEvt(5) / VFD Comm(9)

The

VFD/Comm Failure menu is displayed below:

VFD Proof Time: ###s
VFD COMM Pr Tm: ###s
OK: $(Y/N)
See following table for all

VFD/COMM FAILURE menu items.

VFD/Comm Failure Menu Items

Menu Item

Variable

Default Range Field

Value

VFD

VFD Proof Time: ###s

30

30-999

Comm

The proof timer prior to setting the VFD fail

Failure

alarm, in seconds.

VFD COMM Pr Tm: ###s

30

30-999

The proof timer prior to setting the VFD

communication fail alarm, in seconds.