beautypg.com

8 quick access – Bell & Gossett 10 001 265R5 TechnoForce Pump Controller User Manual

Page 51

background image

TECHNOFORCE Installation, Operation, and Maintenance

45

Operation

To view possible causes for alarm/event, press the

HELP key again after the alarm/event is displayed. Refer to

table below for an overview of the possible alarm/event and their respective causes.
Press the

CLEAR key to return to the main screen. After addressing the source of the alarm/event, press

RESET to re-start the system and/or clear the alarm/event.
The controller logs alarm/event as they occur to aid in troubleshooting unobserved alarm/event. Refer to

Section 6.14.0 for alarm/event logging information
Help Screen Alarm Help/Help Screen Display

Detailed Description

VFD

Failure

“Check

communication

wiring,

and

VFD

display”


High Level

“Check setting of level switch”


High Suction

“Check setting of the HIGH

SUCTION switch” or high suction

settings in the ALARM/EVENTS

set up

High System

“Check system pressure –

manual RESET required”

Low System

“Check system pressure”


Low Suction

“Check setting of the low suction

switch” or low suction settings in the

ALARM/EVENTS set up

Low Level

“Check setting of level switch”


NFSD

“System will restart automatically

when flow occurs”


Pump Fail

“Check DP switch, impeller, coupler,

motor”


Sensor Fail

“Check wiring, piping, polarity,

continuity”
Sensor Reading

“Check wiring of both sensors, and

Drift

compare the pressure reading of both

sensors with pressure gauge ”

Low Battery

Replace OIP battery

Replace OIP battery

The controller is not receiving a closed run

signal from VFD number X after it has been

given a start command or communication

failure or VFD fault
Check for open or closed contacts, refer to

wire diagram for proper connection.
Check for open or closed contacts and high

suction settings, refer to wire diagram for

proper connection

Check the pressure setting in the setup

menu.
Check the pressure setting in the setup

menu.
Check for open or closed contacts and low

suction settings, refer to wire diagram for

proper connection
Check for open or closed contacts, refer to

wire diagram for proper connection.
Check the Reset PSI Drop value and the

pressure sensor connections, refer to the

wire diagram.
The controller is receiving a closed signal

from the differential pressure switch for

pump number X after it has been given a

start command
The controller is not receiving the proper

4-20mA
“Check wiring of both sensors, and compare

the pressure reading of both sensors with

pressure gauge ”

5.8 Quick Access

Using quick access function user can directly jump to the setup screen need to be setup. To use this function

press

QUICK ACCESS/6 key from status screen. The display now shows.

Enter Page ####
Exit $ (Y/N)
Press

NO/0 to edit the page number. Enter the screen number need to be access and press the ENTER key.

It will lead to the setup screen entered. Refer the appendix for the quick access screen numbers.