Bell & Gossett 10 001 265R5 TechnoForce Pump Controller User Manual
Page 40

TECHNOFORCE Installation, Operation, and Maintenance
34
Installation
4.10.41 Low system pressure
Paths: Status Screens / Set up(3) / AlrmEvt(5) / Low System(2)
The Low System Pressure menu is displayed below:
Low Sys Press: ##PSI
Low Sys Pr Tm: ##s
Alarm: $ Stop Pumps: $
OK? $ (Y/N)
See following table for all
LOW SYSTEM PRESSURE menu items.
Low System Pressure Menu Items
Menu Item
Variable
Default Range Field
Value
Low
Low Sys Press: ### PSI
32
0-999
System
The pressure below which an alarm or
Pressure
event will be set, in PSI
Low Sys PrTm: ###s
0
0-999
The proof timer prior to setting an alarm or event, in
seconds. A value of 0 disables this alarm or event.
Alarm: $
N
Y/N
Set this value to “Y” to consider low system pressure
an alarm, or set it to “N” to consider it an event.
Stop Pumps: $
N
Y/N
Set this value to “Y” to stop all pumps in the event of
a low pressure alarm or event. Set it to “N” to continue
operation normally during this alarm or event.
4.10.42 High system pressure
Paths: Status Screens / Set up(3) / AlrmEvt(5) / High System(3)
The High System Pressure menu is displayed below:
High Sys Press: ##
High Sys Pr Tm: ##s
OK? $ (Y/N)
See following table for all
HIGH SYSTEM PRESSURE menu items.
High System Pressure Menu Items
Menu Item
Variable
Default Range Field
Value
High System
High Sys Press: ### PSI
112
0-999
Pressure
The pressure above which an alarm will be set, in PSI.
High Sys Pr Tm: ##s
20
0-999
The proof timer prior to setting an alarm, in seconds,
A value of 0 will disable this alarm.