TECHNOFORCE Installation, Operation, and Maintenance

34

Installation

4.10.41 Low system pressure

Paths: Status Screens / Set up(3) / AlrmEvt(5) / Low System(2)

The Low System Pressure menu is displayed below:
Low Sys Press: ##PSI
Low Sys Pr Tm: ##s
Alarm: $ Stop Pumps: $
OK? $ (Y/N)
See following table for all

LOW SYSTEM PRESSURE menu items.

Low System Pressure Menu Items

Menu Item

Variable

Default Range Field

Value

Low

Low Sys Press: ### PSI

32

0-999

System

The pressure below which an alarm or

Pressure

event will be set, in PSI

Low Sys PrTm: ###s

0

0-999

The proof timer prior to setting an alarm or event, in

seconds. A value of 0 disables this alarm or event.

Alarm: $

N

Y/N

Set this value to “Y” to consider low system pressure

an alarm, or set it to “N” to consider it an event.

Stop Pumps: $

N

Y/N

Set this value to “Y” to stop all pumps in the event of

a low pressure alarm or event. Set it to “N” to continue

operation normally during this alarm or event.

4.10.42 High system pressure

Paths: Status Screens / Set up(3) / AlrmEvt(5) / High System(3)

The High System Pressure menu is displayed below:
High Sys Press: ##
High Sys Pr Tm: ##s
OK? $ (Y/N)
See following table for all

HIGH SYSTEM PRESSURE menu items.

High System Pressure Menu Items

Menu Item

Variable

Default Range Field

Value

High System

High Sys Press: ### PSI

112

0-999

Pressure

The pressure above which an alarm will be set, in PSI.

High Sys Pr Tm: ##s

20

0-999

The proof timer prior to setting an alarm, in seconds,

A value of 0 will disable this alarm.