24. Fuel Train
250
PNEG-707 12', 18', 24' and 30' GSI Commercial Tower Dryer
Installation Guidelines
NOTE: Fuel train components will be wired to electrical control system (by electricians), so locate fuel
train as close as possible to electrical control system.
Mount fuel train on two(2) or three(3) stands as required. Mark, cut, and drill to adapt fuel train stands to
meet specific site requirements.
Check during installation to keep fuel train level.
As required, break apart fuel train components, and install as shown in
, fuel train.
IMPORTANT: Seal all threaded pipe connections with heavy duty pipe sealing compound.
Check arrows (or other fuel intake direction indicators) on all fuel train components. Be sure all arrows
point in direction of fuel flow.
IMPORTANT: Until fuel train installation on stands is complete, support components securely at all times.
Figure 24M Seal all threaded pipe connections with
heavy duty pipe sealing compound.
Figure 24N As required, break apart fuel train
components, and install as shown in
, fuel train.
Figure 24O
IMPORTANT: Be careful not to cross thread pipe to union.