4. CONNECTIONS

4.5 Alarm Output Terminals


These terminals are for the alarm output (option), which is (1) MOS relay type, (2) mechanical relay “c” contact
type or (3) mechanical relay “a” contact type. The mechanical relay “c” contact type does not conform to the
international safety standards.

1

Alarm output terminals

The terminal arrangement depends upon the type
of alarm output.

Terminal and relay No.

Terminal block

RD200

RD2800

1

No. 1 to 6

No. 1 to 6

2

No. 1 to 12

[Remarks]Only one terminal block is provided for
the remote contacts terminals.

2

Connections

Turn off the power supply and buffer relay power
supply before the connections for preventing an
electric shock.
(1) Connect cables to a load via a buffer relay.
(2) Use cables with crimp style terminals and

insulation sleeves for the alarm output
terminals.


The alarm output of your recorder may
become defective. This may be caused by
wrong operation, failure or other abnormal
inputs. Take safety measures against an
output failure before use if necessary.


3

Cautions on connections

1) Output contact rating
(1) MOS relay

Maximum voltage

240 V (AC, DC)

Maximum current

50 mA (AC, DC)

(2) Mechanical relay

Power supply Resistive load Inductive load

100 VAC

0.5 A

0.2 A

240 V AC

0.2 A

0.1 A

100 V DC

0.3 A

0.1 A

MOS relay/Mechanical

relay “a” contact

Mechanical relay “c”

contact









* N.C terminal: Only for the mechanical relay “c” contact
output




A buffer relay power supply is applied to the
alarm output terminals after connections. Don’t
touch these terminals for preventing an electric
shock. Make sure to mount the terminal cover
after connection.

2) Mounting of contact protective element

(1) Mount a contact protective element

conforming to the buffer relay.

(2) To prevent a malfunction being caused by a

light load, the most effective mounting position
for the element is on the coil side of the buffer
relay ('a' in the above diagrams)

(3) The MOS relay will be broken, even if a

signal exceeding the contact rating is
momentarily applied.

Take safety measures.

b

a

Buffer relay

Your recorder

N.O

COM

N.C

*

: Contact protective element (It is
recommended to mount this
element on the “a” side.)

N.O

COM

N.C

1 2 3 4 5 6

1 2 3 4 5 6

Remote
contacts

N.O

COM

Remote
contacts

Caution

mark for alarm output terminals

Warning

Load

Power supply

1 2 3 4 5 6