19. HARDWARE CHECK

19.5 Alarm Output Check


This check is only available for the alarm output (option). It checks the relay drive circuits and relays by outputting
the shorted (on) or open (off) signals at the specified alarm output terminals (relay Nos.).

Check Flow Chart

Operation screen

[Engineering mode selection]

( + )

3 sec. or more

   

[Selecting check]


   

[Displaying check 1]

    

[Displaying check 2]

    

[Selecting alarm output]

   

[Displaying replay No.]

   

[Programming relay No.]

~ →

  

[Selecting output]

    

Confirming output












* N.C terminals are provided for the

mechanical relay “c” contact output.



Output

Output

condition

N.O - COM

Off

10M

Ω or

more

MOS relay

On

50

Ω or less

Off

10M

Ω or

more

Mechanical relay

(Common for “a”
and “c” contacts)

On

0.1

Ω ore less




Press or to switch
Check 1 and 2.



(1): Alarm output check
(2): Remote contacts input check
(3): Communications interface check



The programming range of relay Nos.
are 1 to 6 for AL and 01 to 12 for AH.



The selection of output (on or off) is
effective at the moment is
pressed. The previous output status is
kept until then.

Cursor

Check

Cursor

(1) (3)

(2)

Cursor

Cursor

Relay No.

Open

Short circuiting

Resistance values between terminals

Relay No. for alarm output terminals

DISP

°C

°F

ENTRY

%

/

°C

°F

ENTRY

0

CLEAR

6

A - Z

ENTRY

ENTRY

%

/

ENTRY

Cursor

Cursor

Cursor

Ref. 1

Ref. 2

Ref. 3

Ref. 4

Types of check 2

Reference 2

Check 1 and 2 switching

Reference 1

Programming relay No.

Reference 3

Output

Reference 4

2 sec. or more

SHIFT

6

A – Z