Page 58: 7 d/a monitor option d1

background image

Start-up manual

COMPAX-M / -S

D/A monitor option D1

58

10V

*

VS

BG

*

MW

PG

=

PG:

physical parameter

MW:

voltage on output channel in [V]

BG:

reference value from the above table

VS:

gain factor

P76 = 4.000 0010 P77 = 13.000 0005
Therefore the following applies:

channel 2: measuring parameter 4 (actual speed value).
gain factor = 10
channel 3: measuring parameter 13 (phase current for phase U).
gain factor = 5

measured values:

channel 0:MW=2.5V=>

10V

*

10

20000min

*

2,5

PG

1

=

=500 rpm

channel 1: MW = 3V =>

10V

*

5

200A

*

3

PG

=

= 12A

The parameters of the D/A monitor can also be set to status S15 or be viewed via
the optimization display (see Page 133).

7.9.7 D/A monitor option D1

The option D1 cannot be used for COMPAX 1000SL.

This option provides you with two additional analogue output channels with a
resolution of 12 bit. These channels are updated every 100 µs. Use the parameters
P73 and P74 (as you do with the service D/A monitor) to select 2 quantities and to
adapt them to the required measuring range using 2 parameters (P71 and P72).
D/A monitor option D1 must be ordered as a separate item.
To obtain output from the measured signals, you will need an externally connected
monitor box (ASS1/01) with 2 BNC bushes for connecting the measurement
instruments. This is connected as follows:

!

monitor box is connected to COMPAX connector X17.

!

the initiator line is connected from X17 to the monitor box. The signals are fed
through the monitor box.

Meaning and range of values of P71 - P74

No.

Parameter

Range

P71

Gain factor from channel 0.

1...10 000

P72

Gain factor from channel 1.

1...10 000

P73

Measuring parameter of channel 0. (For the meaning, see
table on Page 56).

0...18

P74

Measuring parameter of channel 1. (For the meaning, see
table on Page 56).

0...18

The parameter can only be actuated once you have entered the password.

Example:P71=10 P72=5

P73=4

P74=13

Therefore, the following applies:

channel 0: measuring parameter 4 (actual speed value).
gain factor = 10
channel 1: measuring parameter 13 (phase current for phase U).
gain factor = 5

Calculation of

physical parameter

using the measured

value:

Example:

The measuring

parameters are

selected using P73

or P74