Error handling and error messages

225

Unit

hardware

Connector

assignment / cable

Technical data

Configuration

Positioning and

control functions

Optimization

functions

Interfaces

Accessories /

options

Status

Parameter

Error List:

No.

Cause

Action

Acknow-

ledge with

Drive

volt.-free

E48 Motor thermostatic switch reports

error.

Check resolver cable, motor type and motor / remove
external sources of heat.

Power on

yes

E49 Motor or drive reports blockage.

Drive remains in the current limit
(P16) for longer than P108

Free mechanics. This error message can be
switched off by setting P13="0".
Check motor cable.

Quit

yes

COMPAX-S: speed controller
oscillating

Optimize controller (reduce P23 stiffness).

E50 Limit switch 1 activated.

Move by hand or POSA from limit switch.

Quit

no

E51 Limit switch 2 activated.

Move by hand or POSA from limit switch.

see
P217

Quit

no

E52 Error in emergency stop circuit.

Check emergency stop switch contacts.

Quit

yes

E53 Motor overloaded.

Check dimensions.

Quit

yes

E54 Speed higher than the maximum

motor speed or higher than P15 *
1.21

Reduce nominal speed or, if speed is too high due to
harmonies, optimize controller.

Quit

yes

E55 External emergency stop.

Intermediate circuit not enabled.
Temperature overload.

Check system, then switch unit on again.
Voltage must be at least 2s >320V.
External load too great.

Quit

yes

E56 Emergency stop directly in

COMPAX-M via X9/6 (switched on
via P219=7)

Check system, then switch unit on again.

Quit

yes

E57 Voltage in intermediate circuit too

low (<70V).

Check mains connection.
Switch off E57 using P218 ="1".

Quit

yes

E58 Temperature is too high (>75°) or

SinCos

- temperature error

Increase acceleration times.

Quit

no

E65 Encoder error

Check encoder cable.
Axis is brought to a stop through speed control.
(switch off using P218)

Quit

no

E76 HEDA synchronisation interrupted

Check physical connection and P249

Quit

no

E77 HEDA transmission error

Check physical connection and P247

Quit

no

E78 Successive HEDA transmission

errors

Check physical connection and P248

Quit

no

Negative command acknowledgement (only for warnings)

E72 Block Check Character - error or

general fault.

Re-send the characters

*

no

E90 Syntax error; command not valid

Check command structure.

*

no

E91 Command cannot be executed in this

COMPAX operating mode.

Check COMPAX status

*

no

E92 Function running, command cannot

be executed

*

no

E93 Data record memory active,

command cannot be executed

*

no

E94 Password missing

*

no

* Quit is not required.

Response to lag error (error E10)
Position controller

COMPAX is switched from position control mode to speed control mode and speed 0 specified. The drive
remains powered. (Does not apply for COMPAX xx60)
The next move command after the error acknowledgement brings the system back to position control.

Response to E15

COMPAX is switched from position control mode to speed control mode and speed 0 specified. The drive
remains powered.

Speed controller

In speed control mode, control is referenced to speed 0.