beautypg.com

Mains module nmd10/nmd20, Overview nmd, Dimensions / installation – Parker Products COMPAX-M /-S (L) User Manual

Page 22: Start-up manual, Compax-m / -s, 1 overview nmd, 2 dimensions / installation, Version

background image

Start-up manual

COMPAX-M / -S

22

7.3

Mains module NMD10/NMD20

The mains module ensures the supply of current to the COMPAX-M (not COMPAX
35XXM) axis controller and the SV drive connected into the network. It is
connected to the 3-phase power supply with 3 * 400V AC and PE. 24V DC voltage
must be provided for the control electronics.

7.3.1 Overview

NMD

L1

L2

L3

PE

24V

PE

+

-

X1

X2

X3

X4

24V

+

-

+

-

24V

PE

+LS

-LS

PE

+LS

-LS

X6

Ready

Error

X7

IN

OUT

RS 485

X8

Control

Power Supply

X8 Control

X7 bus-systems

OUT

X4 control- and

status-signals

Bus signals

continuation

X3 control

voltage 24 V

X2 power inter-

mediate loop

voltage supply
3*(80-500)V AC/
X1 24V CC

X6 bus-

systems IN

X18 fan

Before wiring up, always de-energize the unit.

Even once the mains supply has been switched off, dangerous
levels of voltage can remain in the system for up to 5 min.

The PE connection must be a 10mm

2

version

7.3.2 Dimensions / installation

Dimensions and installation of the NMD10 and NMD20 power units correspond to
the data for COMPAX-M (see Page 20).