beautypg.com

Start-up manual, Compax-m / -s – Parker Products COMPAX-M /-S (L) User Manual

Page 38

background image

Start-up manual

COMPAX-M / -S

38

The final stage is enabled using a bridge between X3/1 - X3/1.
If this connection is missing, the final stage is voltage-free and error message E40
appears (see from Page 223).

!

Energy recuperated during braking is stored in the supply capacitors. The
capacity and storable energy is:

COMPAX 45XXS: 330µF/52 Ws
COMPAX 85XXS: 500µF/80 Ws

If the recuperated energy causes overvoltage, then the internal ballast resistance is
engaged.

Enable internal ballast resistance: X2/5 - X2/6
The internal ballast resistance is enabled by a bridge between X2/5 and X2/6.
If this connection is missing, the controller operates without ballast resistance; in
braking mode, error message E38 may appear (see from Page 223).

Braking power

Duration

Cooling

down time

COMPAX 45/85S: 300W

unlimited

1.5 kW

<10s

10s

We provide external ballast resistances for COMPAX 45XXS / 85XXS (see
Page 193).

Connecting a ballast resistance to COMPAX 4500S/ COMPAX 8500S
The ballast resistance is connected to HV, T

D

and PE.

The output is protected from short circuits.
Note!
When an external ballast resistance is connected, the bridge between R

D

and T

D

must be removed.

Enable bridges:

X3/1 - X3/2

Overvoltage

limitation

Maximum braking

power of the

internal ballast

resistance