Appendix, Compax-m/s – Parker Products COMPAX-M /-S (L) User Manual

Page 224

background image

Appendix

COMPAX-M/S

Monitoring and limitation characteristics

224

No.

Cause

Action

Acknow-

ledge with

Drive

volt.-free

E23 The current command is not allowed.

Positioning command in the speed control mode.

Approach MZ in speed control mode.

Travel command when drive is switched off.

Hand +/- when an error is present.

More than 8 consecutive comparator commands

(preparatory commands) in the data record
memory.

Quit

no

E24 The speed selected is not valid.

Enter speed between 0...100%.

Quit

no

E25 The position selected is not valid.

Note end limits and "Software end limit monitoring"
chapter in variant documentation.

Quit

no

E26 REPEAT without END or GOSUB

without RETURN .

Insert END / RETURN command.

Quit

no

E27 Parameter must not be written.

Check parameter.

Quit

no

E29 Motor values missing.

Send unit to HAUSER.

Quit

yes

E30 Hardware fault.

Remove extreme external sources of fault.

Quit

yes

E31 Error in parameters.

Check parameter.

Quit

no

E32 Error in parameters.

Check parameter.

Quit

no

E33 Error in program memory.

Check data record memory.

Quit

no

E34 Error in program memory.

Check data record memory.

Quit

no

E35 Hardware fault.

Remove extreme external sources of fault.

Quit

no

E36 Hardware fault.

Faulty or incorrect unit hardware.

Power on

yes

E37 Auxiliary voltage +15 V missing.

Switch on again.

Power on

yes

E38 Voltage in intermediate circuit too

high; e.g. if braking output is too
high. Limits:
COMPAX 25XXS: >400V
COMPAX 10XXSL: >400V
otherwise: >800V

Increase braking and idle times / check mains power.
COMPAX 25XXS: external ballast resistance
missing.
COMPAX 45XXS/85XXS: bridges X2/5 - X2/6
missing.
COMPAX 1000SL: Check value P134.

Quit

yes

E39 Temperature too high (>85°), cycle

too hard.

Increase acceleration times.

Quit

yes

E40 Input "Enable final stage"

(45/85S: X3/1-/2; 1000SL X19/24-X19/12, 35XXM: X19/9-/10)

not assigned

Only with COMPAX 35XXM, COMPAX 45XXS, COMPAX 85XXS and COMPAX 1000SL!

Note!
With E40 there is no braking delay; the final stage is immediately switched off.
The input has a direct effect on the hardware.

Quit

yes

E41 Final stage reports error.

COMPAX 35XXM: Short circuit of the
ballast resistance or undervoltage
24V
COMPAX 1000SL:
Overvoltage or ballast switching

Check motor and cable for ground fault, short circuit
fault and function; remove extreme external sources
of fault.

Quit

yes

E42 Resolver / sensor error.

Check resolver cable and connector for correct
connections and faults.
A special error code can be found in channel 67 of
the optimization display. This means
Error No. 1 ... 30: Sensor indicates error
Error No. > 30:

COMPAX indicates error

Error No. =160: Sensor level too high
Error No. =161: Sensor level too low
(implement level adaptation using parameter P131)

Quit

yes

E43 Output overloaded.

Check I/O cables, connectors and external circuits.
Note load limits (refer to start-up manual).

Quit

yes

E44 Positive auxiliary voltage outside

tolerances.

Switch unit on again.

Power on

yes

E45 Negative auxiliary voltage outside

tolerances.

Switch unit on again.

Power on

yes

E46 Supply voltage +24V is too high.

Check +24V DC power unit.

Power on

yes

E47 Supply voltage +24V is too low.

Check +24V DC power unit.

Power on

yes

Please note: the operating instructions (pages 67 - 171) as well as the application examples (pages
225 - 237) can be found in the complete product manual which is available as PDF file on CD