beautypg.com

Function of outputs, Interfaces, 7 function of outputs – Parker Products COMPAX-M /-S (L) User Manual

Page 153

background image

Interfaces

Digital inputs and outputs

153

Unit

hardware

Connector

assignment / cable

Technical data

Configuration

Positioning and

control functions

Optimization

functions

Interfaces

Accessories /

options

Status

Parameter

Error list

8.6.1.7 Function

of

outputs

O1

O1="1" if there is no error for group E1 ... E57.

O1="0" if there is an error for group E1 ... E57; the drive does not accept

positioning commands.

O2

O2="1" if there are no errors

E58.

O2="0" if there is an error

E58.

O2 is assigned the "Idle display" function via P227 bit 1="1" (see Page ).119

O3

When "1" is displayed, this indicates that a reference system has been defined,

i.e. there is information about the position of machine zero.

When in "Normal mode", positioning is only possible when O3="1".

By using an absolute value sensor and the relevant option (O1), O3="1" remains

as such even if the unit has been switched off in the meantime.

Once the "Find machine zero" function has been activated (I1&I2="1"), O3="0"

until machine zero is found.

O4

"Ready for START" is used for program control.

O4 is set,

if the program is at a WAIT START instruction and waiting for the START signal,

after an interruption with STOP or BREAK and these signals are no longer

present,

after a corrected error condition and

after Power On.

at program end with the END command.

O4 has no significance for direct command specifications.

O5

O5 is set to "0" when starting a positioning process; this applies for POSA,

POSR, WAIT POSA, WAIT POSR, approach real zero, approach machine zero,
Hand+, Hand-.

O5 is set once the positioning has been completed in the correct manner. This

applies for POSA, POSR, WAIT POSA, WAIT POSR, approach real zero.
POSR 0 causes the brief resetting of O5.

Conditions for O5="1":

The actual position value is in the positioning window (+/-P14) and

the nominal value sensor has reached the target point of the nominal value

specification.

O5 is set in speed control mode, if the nominal value generator has processed

the speed ramp.

No fault

No warning

Machine zero
has been
approached

Ready for start

Position
reached