Optimization functions

External position localization with position adjustment

137

Unit

hardware

Connector

assignment / cable

Technical data

Configuration

Positioning and

control functions

Optimization

functions

Interfaces

Accessories /

options

Status

Parameter

Error list

Para-
meter

Meaning

valid
from..

P214

Encoder direction.
="0": positive direction for encoder rotating clockwise.
="1": positive direction for encoder rotating anti-clockwise.
Setting aid:

Switch off external position adjustment (P144=4) and data record

P214=0.

Note S42 (position of external sensor).

Proceed with POSR x axis.

S1 and S42 must change by the same value (x).

If the prefix of the modification is different, set data record P214="1".

If the modification has a different amount, check P143 and P98.

VP

The command "SPEED SYNC" cannot be used in external position
localization!

A number overrun is possible in special applications. To prevent this occurring, the
following condition must be met:

V

≥≥≥≥

1

Determine V depending on drive type and measuring unit:

Drive type

Measuring unit Determining V

Spindle drive

mm (inch)

)

4

.

25

(

85

P

K

V

=

Rack-and-pinion/
toothed belt

mm (inch)

)

4

.

25

(

82

P

85

P

K

V

=

General drive

mm (inch)

)

4

.

25

(

1000

K

V

=

General drive

Incr.

V K

=

A slip filter with a differentiating element (D-element) is provided to optimize
external position adjustment.
No.

Meaning

Unit

Minimum

value

Default

value

Maximum

value

Valid

from...

P67

D-element slip filter

%

0

100

500

VP

P68

Slip filter lag

%

0

100

5000

VP

Both parameters are set to 100% as standard. The time constants are then
identical and the filter ineffective. Meaning:

Parameter

Effect

Application

P67 = P68

Filter ineffective (standard)

P67 < P68 or
P67 = 0

Filter has
delaying effect

Low resolution of measuring system

Interference on the measuring signal

P67 > P68

Filter has
differentiating
effect

at high dynamic requirements.

Conditions:

high-resolution measuring

system and low interference on the measuring
signal.

Limit values of
parameters

Slip filter for
external
position
localization

Using

K

P

P

P

=

98 16384

83

143

.