Page 77

background image

Wiring the S7-400

4-17

Automation System S7-400 Hardware and Installation

A5E00850741-01

4.11

Wiring Rules

Lines and Tools

For wiring the S7-400 modules, there are some rules for the cables and tools to

use.

Rules for

... Power Supply

... Front Connectors

Crimp terminal

Screw-type

terminal

Spring-type terminal

Conductor

cross-sections:
Outer diameter:

3 to 9 mm

Flexible cond.

without wire end

ferrule

no

0.5 to 1.5 mm

2

0.25 to 2.5 mm

2

0.08 to 2.5 mm

2

Flexible cond. with

wire end ferrule

230 VAC: flexible

sheathed cable

3 x 1.5 mm

2

24 VDC: flexible

sheathed cable

3 x 1.5 mm

2

or

individual wires

1.5 mm

2

no

0.25 to 1.5 mm

2

0.25 to 1.5 mm

2

No. of conductors

per terminal

1

1

1

*

1

*

Stripping length of

single conductors

7 mm

5 mm

8 to 10 mm without

ferrule

10 mm with ferrule

8 to 10 mm without

ferrule

10 mm with ferrule

Wire end ferrules

230 VAC: with

insulating collar to

DIN 46228 E1,5-8
24 VDC: without

insulating collar to

DIN 46228, shape A,

short version

-

with or without

insulating collar to

DIN 46228 Part 1

or 4, Shape A,

normal version

with or without

insulating collar to

DIN 46228 Part 1 or

4, Shape A, normal

version

Blade width and

shape of the screw

driver

3.5 mm (cylindrical

shape)

-

3.5 mm (cylindrical

shape)

0.5 mm x 3.5 mm

DIN 5264

Tightening torque:

for connecting

conductors

0.6 to 0.8 Nm

-

0.6 to 0.8 Nm

-

*

You can also connect a combination of two conductors of up to 1.0 mm each to a screw-type

or spring-loaded terminal. You must use special wire end ferrules for this purpose. Two types

and manufacturers of such ferrules are given below:

• Phoenix TWIN

Type no. 32 00 81 0, for 2 x 1 mm

2

• AMP

Order no. 966 144-4, for 2 x 1 mm

2

Note
You must use shielded cables for the analog modules (see Section A.5).