Networking

5-15

Automation System S7-400 Hardware and Installation

A5E00850741-01

5.4

Cable Lengths

Segment in the MPI Network

In a segment of an MPI network, you can use cable lengths of up to 50 m. This
50 m applies from the first node to the last node in the segment.

Table 5-1

Permitted Cable Length of a Segment in an MPI Network

Transmission Rate

Maximum Cable Length of a Segment (in m)

187.5 Kbps

50

19.2 Kbps

50

12 Mbps

50

Segment in the PROFIBUS-DP Network

In a segment of a PROFIBUS-DP network, the cable length depends on the
transmission rate (see Table 5-2). These lengths only apply if you connect a CPU
to a PROFIBUS-DP network via an MPI interface configured as a DP interface.

Table 5-2

Permitted Cable Length of a Segment in the PROFIBUS-DP Network

Depending on the Transmisson Rate

Transmission Rate

Maximum Cable Length of a Segment (in m)

9.6 to 187.5 Kbps

1000

500 Kbps

400

1.5 Mbps

200

3 to 12 Mbps

100

Longer Cable Lengths

If you have to implement cable lengths which are longer than permissible in one
segment, you must interconnect RS 485 repeaters. The maximum possible cable
length between two RS 485 repeaters is the same as the cable length of a segment
(see Tables 5-1 and 5-2). With these maximum cable lengths, however, note that
no other nodes may be situated between the two RS 485 repeaters. You can
connect up to ten RS 485 repeaters in series.

Note that you must count an RS 485 repeater as a node of the MPI network in the
total number of all nodes to be connected, even if it is not assigned its own
MPI number. The use of RS 485 repeaters reduces the number of nodes.