A.10

How to Protect Digital Output Modules against
Inductive Surge

Inductive Surge Voltage

Overvoltage occurs when inductive devices are switched off. Examples are relay
coils and contactors

Integrated Surge Arrester

S7-400 digital output modules are equipped with an integrated surge arrester

Additional Overvoltage Protection

Inductive devices require additional surge arresters only in following cases:

• If SIMATIC output circuits can be switched off by additionally installed contacts

(e.g. relay contacts).

• If the inductive loads are not controlled by SIMATIC modules.
Note: Consult the supplier of the inductors for the ratings of surge suppression
devices.

Example

Figure A-8 shows an output circuit that requires additional surge arresters.

Contact in output circuit

Inductivitys requires a circuiting

(see Figures A-9 and A-10)

D

Figure A-8

Relay Contact for EMERGENCY OFF in the Output Circuit