beautypg.com

Siemens Automation System S7-400 User Manual

Page 192

background image

Assembling and Installing Systems

A-24

Automation System S7-400 Hardware and Installation

A5E00850741-01

Table A-3

High-Voltage Protection of Cables with the Help of Surge Protection Equipment, continued

Ser.

No.

Order No.

... equip transition point 0 <--> 1

with:

Cables for ...

AC TT system

1 piece of

DEHNbloc/1 lightning
conductor
phase to N

900 111*
5SD7 032

1 piece of

DEHNgap B/n N-PE light-
ning conductor
N to PE

900 130*

2

24 VDC Power Supply

1 piece of

Blitzductor VT lightning
conductor,
type A D 24 V --

918 402*

3

MPI bus cable, RS 485, RS 232
(V.24)

1 piece of

Blitzductor CT lightning
conductor, type B

919 506* and
919 510*

4

Inputs/outputs of digital modules
24 V

DEHNrail 24 FML

901 104*

5

24 VDC power supply module

1 piece of

Blitzductor VT lightning
conductor,
type AD 24 V --

918 402*
900 111*
5SD7 032

6

Inputs/outputs of digital modules and
120/230 VAC power supply

2 pieces of DEHNbloc/1 lightning

conductor

900 111*
5SD7 032

7

Inputs/outputs of analog modules up
to 12 V +/--

1 piece of

Blitzductor CT lightning
conductor,
type B

919 506* and
919 510*

* You can order these components directly at:

DEHN + SÖHNE

GmbH + Co. KG

Elektrotechnische Fabrik

Hans-Dehn-Str. 1

D-92318 Neumarkt