Wiring the S7-400

4-2

Automation System S7-400 Hardware and Installation

A5E00850741-01

4.1

Supplying Power to Modules

Power Supply Modules and Load Current Power Supplies

The modules of the S7-400 system are supplied with all the required operating
voltages by a power supply module, via the backplane bus of the rack. Which
power supply module you use in a rack depends on your system requirements (line
voltage, current consumption of the modules used).

You must provide load voltages and currents via external load current power
supplies.

The following figure shows how the individual modules of the S7-400 are supplied
with current and voltage.

S7-400
power supply

module

S7-400
modules (DC

or AC)

Operating voltages
5 VDC and 24 VDC

via backplane bus

Load current via

front connector

Load current power

supply

Line voltage:

120/230 VAC

with supply

isolator

or 24 VDC

Note
The power supply modules must not be connected in parallel on their secondary