A.9.1

Lightning Protection Zone Concept

Principle of the Lightning Protection Zone Concept According to IEC 61312-1/DIN

VDE 0185 T103

The principle of the lightning protection zone concept states that the volume to be
protected, for example, a manufacturing hall, is subdivided into lightning protection
zones in accordance with EMC guidelines (see Figure A-6).

The individual lightning protection zones are constituted by the following measures:

The external lightning protection of the building (field side)

Lightning protection

zone 0

The shielding of buildings

Lightning protection

zone 1

The shielding of rooms

Lightning protection

zone 2

The shielding of devices

Lightning protection

zone 3

Effects of a Lightning Strike

Direct lightning strikes occur in lightning protection zone 0. The lightning strike
creates high-energy electromagnetic fields which can be reduced or removed from
one lightning protection zone to the next by suitable lightning protection
elements/measures.

Surges

In lightning protection zones 1 and higher, surges can result from switching
operations and interference.