Installing the S7-400

2-28

Automation System S7-400 Hardware and Installation

A5E00850741-01

Example of selecting the cabinet type

The example below clarifies the maximum permissible ambient temperature at a
particular power loss for various cabinet types.

Equipment suitable for installation in a cabinet:

1 central rack

150 W

2 expansion racks, 150 Watts each

300 W

1 load current power supply under full load

200 W

Accumulated power loss

650 W

Permissible ambient temperatures at an accumulated power loss as shown in
Figure 2-2:

Type of Cabinet

Max. Permissible Ambient

Temperature

Closed, with natural convection and forced circulation

(Curve 3)

(no operation possible)

Open, with through-ventilation (Curve 2)

approx. 38° C

Closed, with heat exchanger (Curve 1)

approx. 45° C

Cabinet dimensions

Vital dimensional design factors for an S7-400 cabinet

• Space requirement of the racks

• Minimum clearance between racks and cabinet walls

• Minimum clearance between racks

• Space requirement of cable ducts or fan subassemblies

• Locations of rails