beautypg.com

5 profibus- dp bus cables, 5 profibus-dp bus cables – Siemens Automation System S7-400 User Manual

Page 116

background image

Networking

5-18

Automation System S7-400 Hardware and Installation

A5E00850741-01

5.5

PROFIBUS-DP Bus Cables

PROFIBUS-DP Bus Cables

Siemens supply the following PROFIBUS-DP bus cables (see catalog ST 70):

PROFIBUS-DP bus cable

6XV1830-0AH10

PROFIBUS-DP cable for burying in ground

6XV1830-3AH10

PROFIBUS-DP trailing cable

6XV1830-3BH10

PROFIBUS-DP bus cable with PE sheath (for foodstuffs and

luxury food industry)

6XV1830-0BH10

PROFIBUS-DP bus cable festoons

6XV1830-3CH10

Characteristics of the PROFIBUS-DP Bus Cable

The PROFIBUS-DP bus cable is a twisted, shielded pair with the following
characteristics:

Characteristics

Values

Impedance

approx. 135 to 160 Ω (f = 3 to 20 MHz)

Loop resistance

≦ 115 Ω/km

Working capacitance

30 nF/km

Attenuation

0.9 dB/100 m (f = 200 kHz)

Permissible core cross-section

0.3 mm

2

to 0.5 mm

2

Permissible cable diameter

8 mm ± 0.5 mm

Rules for Laying Cables

When you lay the PROFIBUS-DP bus cable, you should not:

• Twist it,

• Stretch it, or

• Compress it.
Furthermore, when installing the indoor bus cable, you must observe the following
basic conditions (d

A

= outer diameter of the cable):

Characteristics

Boundary

Conditions

Bending radius for single bend

≥ 80 mm (10 x d

A

)

Bending radius for repeated bends

≥ 160 mm (20 x d

A

)

Permissible temperature range for installation

-- 5 _C to + 50 _C

Storage and stationary operating temperature range

-- 30 _C to + 65 _C