beautypg.com

1 fiber-optic cables – Siemens Automation System S7-400 User Manual

Page 122

background image

Networking

5-24

Automation System S7-400 Hardware and Installation

A5E00850741-01

PROFIBUS Optical Bus Terminal (OBT)

A PROFIBUS node can be connected to the optical PROFIBUS-DP network via a

PROFIBUS Optical Bus Terminal (OBT) (6GK1 500-3AA00) without an integrated

fiber-optic cable interface (e.g. programming devices (PGs) or operator panels

(OPs), see Figure 5-13).
The programming device/PC is connected to the RS 485 interface of the OBT by

means of the PROFIBUS cable. The OBT is integrated in the optical

PROFIBUS-DP line by means of its fiber-optic cable interface.

5.8.1

Fiber-Optic Cables

Features of the Fiber-Optic Cables

Use Siemens plastic and PCF fiber-optic cables with the following features:

Table 5-4

Features of the Fiber-Optic Cables

Description

SIMATIC NET PROFIBUS

Plastic Fiber-Optic

Duplex Conductor

Plastic Fiber-Optic

Standard Cable

PCF Fiber-Optic

Standard Cable

Standard designation

I-VY2P 980/1000

150A

I-VY4Y2P 980/1000

60A

I-VY2K 200/230

10A17+8B20

Field of application

Indoors with a low

mechanical load,

such as laboratory

test assemblies or in

cabinets:
Cable lengths up to

50 m

Indoor applications:
Cable lengths up to

50 m

Indoor applications:
Cable lengths up to

300 m

Fiber type

Step-index fiber

Core diameter

980 μm

200 μm

Core material

Polymethyl methacrylate (PMMA)

Quartz glass

Cladding outer diameter

1000 μm

230 μm

Cladding material

Fluorinated special polymer

Inner sheath

Material

Color

Diameter

PVC

Gray

2.2  0.01 mm

PA

Black and orange

2.2 ± 0.01 mm

--

(Without inner sheath)

Outer sheath

Material

Color

--

PVC

Purple

PVC

Purple

Number of fibers

2

Attenuation at
wavelength

≤ 230 dB/km

660 nm

≤ 10 dB/km

660 nm