Assembling and Installing Systems

A-35

Automation System S7-400 Hardware and Installation

A5E00850741-01

Shielding and Grounding under Industrial Conditions

If the monitor and programmable controller are operated under harsh industrial
conditions, you must observe the following:

On the side of the programmable controller:

• Connect the cable shields in the cabinet to the shielding busbar immediately

behind the cable inlet. The following points are important:

-- Strip the video cables without damaging the conductors.
-- Secure the outer braided shield with the largest possible area to the

shielding busbar of the programmable controller (for example, secure the

shielding with metal straps or cable clamps).

• Provide large-area contact between the shielding busbars and the frame or

cabinet wall.

• Connect the shielding busbar to the central grounding point of the cabinet.
On the side of the monitor:

• Isolate electronic ground and chassis ground from each other. Proceed as

follows:

-- Remove the jumper on the monitor to separate the two potentials.
-- Install a contact protection on the video sockets, because with isolated

grounding, a shock--hazard voltage of more than 40 V may develop in this

area.

!

Caution
There is a risk of personal injury.
Shock-hazard voltages may be present at the video sockets of the monitor.
Insulate the sockets.

• Connect the ground clamp of the monitor to the chassis ground.

• Connect the cable shields to the ground clamp of the monitor as follows:

Proceed as follows:

-- Strip the outer cable insulation of the video cables in the region of the ground

clamp of the monitor, without damaging the braided shield.

-- Secure the outer braided shield over a large area to the ground clamp of the

monitor.