Networking

5-3

Automation System S7-400 Hardware and Installation

A5E00850741-01

5.2

Fundamentals

Station = Node

Declaration: All the stations you connect in a network are referred to as nodes in
the following.

Segment

A segment is a bus cable between two terminating resistors. A segment can
contain up to 32 nodes. Furthermore, a segment is limited by the permissible cable
length according to the transmission rate.

Baud Rate

The baud rate (transmission rate) is the speed at which data is transmitted,

expressed in terms of bits per second.
• Baud rates of 19.2 kbps to 12 Mbps are possible for interfaces of the type

MPI/DP.

• Transmission rates of 9.6 kbps to 12 Mbps are possible for interfaces of the

type PROFIBUS-DP.

Note
If you change the parameter assignment of the MPI/DP interface transmission rate,

the new transmission rate remains set even after memory reset, voltage failure or

removing/inserting the CPU.

Connectable Nodes

MPI

PROFIBUS DP

Programming devices (PGs)

Programming devices (PGs)

Operator interfaces (SIMATIC-OP),

WinCC

Operator panels (OPs)*

S7-400

PROFIBUS-DP master, PROFIBUS-DP slaves

S7-300

PROFIBUS-DP slaves

* Not recommended in DP operation