Rules for Connection

When you connect a central rack to expansion racks, you must observe the
following rules:

• You can connect up to 21 ERs of the S7-400 to one CR.

• The ERs are assigned numbers to identify them. The rack number must be set

on the coding switch of the receive IM. Any rack number between 1 and 21 may

be assigned. Numbers must not be duplicated.

• You may insert up to six send IMs in one CR. However, only two send IMs with

5 V transfer are allowed in one CR.

• Each chain connected to the interface of a send IM can comprise up to four ERs

(without 5 V transfer) or one ER (with 5 V transfer).

• The exchange of data via the communication bus is limited to 7 racks, meaning

the CR and ER numbers 1 to 6.

• The maximum (total) cable lengths specified for the type of connection must not

be exceeded.

Type of Connection

Maximum (Total) Cable Length

Local connection with 5 V transfer via

IM 460-1 and IM 461-1

1.5 m

Local connection without 5 V transfer via

IM 460-0 and IM 461-0

5 m

Remote connection via IM 460-3 and

IM 461-3

102.25 m

Remote connection via IM 460-4 and

IM 461-4

605 m