Wiring the S7-400

4-7

Automation System S7-400 Hardware and Installation

A5E00850741-01

4.5

Assembling an S7-400 with Grounded Reference
Potential (M)

Application

You use an S7-400 with grounded reference potential in machines or industrial
plants.

Discharge of Interference Currents

When the S7-400 is configured with a grounded reference potential, any
interference currents are discharged to the chassis ground.

Terminal Connection Model

When delivered, the racks have a detachable metallic connection between the
internal reference potential M of the modules and the frame element of the racks.
Situated behind this connection is an RC network which is placed in the circuit for
the ungrounded configuration. This connection is located at the left edge of the
rack. The terminal for the chassis ground also has an electrical connection to the
frame element.

Shown in Figure 4-2 is an S7-400 configured with grounded reference potential. To
ground the reference potential M, you must connect the chassis ground terminal to
the chassis ground and you must not remove the jumper between reference
potential M and the frame element terminal on the rack.

Metallic connection

Frame element terminal

Chassis ground terminal

RC network

M

6.8 nF

10 MΩ

Detachable

jumper

Reference potential M

Figure 4-2

An S7-400 Configured with Grounded Reference Potential