Installing the S7-400

2-29

Automation System S7-400 Hardware and Installation

A5E00850741-01

2.12

Rules for the Arrangement of Modules

Arrangement of the Modules

You only need to observe two rules for rack mounting of the modules:

• In all racks, the power supply module must always be inserted on the extreme

left (beginning with slot 1). In the UR2-H from slot 1 in both segments.

• The receive IM in the ER must always be inserted on the extreme right. In the

UR2-H at slot 9 once per segment.

Note
Establish whether there are additional regulations applying to all modules not

described in this manual.

The following table shows which modules can be used in the different racks:

Table 2-2

Modules in the different racks

Modules

Racks

Racks

UR1, UR2

UR2-H as

CR

UR1, UR2

as ER

UR2-H

as ER*

CR2,

CR3

ER1, ER2

Power Supply Modules

D

D

D

D

D

CPUs

D

D

Send IMs

D

D

Receive IMs

D

D

D

Signal Modules

D

D

D

D

D

*

No IM 463-2, no adapter module, no power supply module along with the IM 461-1.

Space Requirement of the Racks

In the S7-400 system, there are modules occupying one, two, or three slots (width
25, 50, or 75 mm). Refer to the technical specifications of the module under the
keyword “dimensions” to see how many slots a module occupies.

The mounting depth of a rack fitted with modules is 237 mm maximum.