beautypg.com

Siemens Automation System S7-400 User Manual

Page 136

background image

Commissioning

6-8

Automation System S7-400 Hardware and Installation

A5E00850741-01

Resetting the CPU with the Mode Selector Switch

The mode selector switch is designed as a toggle switch. The following figure
shows all positions of the mode selector switch.

RUN

STOP

MRES

Figure 6-2 Positions of the mode selector switch

Proceed as follows to reset the CPU using the mode switch:

Case A: You want to transfer a new, complete user program to the CPU.

1. Set the switch to STOP setting.

Result: The STOP LED lights up.

2. Set the switch to MRES and hold it there.

Result: The STOP LED is switched off for one second, on for one second, off

for one second and then remains on.

3. Turn the switch back to the STOP setting, then to the MRES setting again within

the next 3 seconds, and back to STOP.
Result: The STOP LED flashes for at least 3 seconds at 2 Hz (reset is being

executed) and then remains lit.

Case B: The CPU requests a reset by slow flashing of the STOP LED at 0.5 Hz
(system reset request, for example, when a memory card has been removed or
inserted).

Set the switch to MRES and then back to STOP.
Result: The STOP LED flashes for at least 3 seconds at 2 Hz (reset is being

executed) and then remains lit.