beautypg.com

3 segmented cr, Properties, I/o bus segment 1 i/o bus segment 2 – Siemens Automation System S7-400 User Manual

Page 24

background image

Installing the S7-400

2-8

Automation System S7-400 Hardware and Installation

A5E00850741-01

2.3

Segmented CR

Properties

The “segmented” characteristic relates to the configuration of the CR. In the
(non-segmented) CR the I/O bus is continuous and interconnects all 18 or 9 slots;
in the segmented CR, however, the I/O bus consists of two I/O bus segments.

A segmented CR has the following important characteristics:

• The communication bus is continuous (global), whilst the I/O bus is divided into

two I/O bus segments of 10 and 8 slots respectively.

• One CPU can be inserted per local bus segment.

• The two CPUs in a segmented CR may be in different operating states.

• The two CPUs can communicate with each other via the communication bus.

• All the modules inserted in a segmented CR are powered by the power supply

module at slot 1.

• Both segments have a common backup battery.
The following figure shows a segmented CR with divided I/O bus and continuous
communication bus.

I/O bus

Segment 1

I/O bus

Segment 2

SEG1

SEG1

SEG1

SEG1

SEG1

SEG1

SEG1

SEG1

SEG1

SEG1

SEG2

SEG2

SEG2

SEG2

SEG2

SEG2

SEG2

SEG2

1

2

3

4

5

6

7

8

9

10

11

12

13

14 15

16

17

18

1

SEG1

11

SEG2