Removable Power Dissipation from Cabinets (Example)

The removable power dissipation from a cabinet is governed by the type of cabinet,
its ambient temperature, and the arrangement of equipment in the cabinet.

Figure 2-2 shows a diagram with guide values for the permissible ambient
temperature of a cabinet measuring 600 x 600 x 2000 mm as a function of power
dissipation. These values only apply if you observe the specified installation
dimensions and clearances for racks. Further information can be found in Siemens
catalogs NV21 and ET1.

200

400

600

800

1000

1200

1400 W

Power dissipation

20

30

40

50

60

Ambient temperature in °C

1

2

3

Figure 2-2

Max. Cabinet Ambient Temperature as a Function of Power Dissipation of

Equipment in the Cabinet

Legend for Figure 2-2:

1. Closed cabinet with heat exchanger;

heat exchanger size 11/6 (920 x 460 x 111 mm)

2. Cabinet with through-ventilation by natural convection
3. Closed cabinet with natural convection and forced circulation by equipment fans

!

Warning
Risk of damage to the modules.
Modules may be damaged as a result of excess ambient temperature.