Wiring the S7-400

4-9

Automation System S7-400 Hardware and Installation

A5E00850741-01

Filtering the 24 VDC Supply

When you power the S7-400 from a battery with the ungrounded configuration, you
must provide interference suppression for the 24 VDC supply. Use a Siemens
power cable filter, such as the B84102-K40.

Insulation Monitoring

If a double fault could cause a hazardous state in the installation, you must provide
insulation monitoring.

Example of Ungrounded Operation

If you have configured an S7-400 with a local connection and you only wish to
ground the overall installation at the CR, you can operate the ERs in an
ungrounded configuration.

Note
If you connect an ER via a local connection with 5 V transfer, ungrounded

operation is mandatory for the ER.