Assembling and Installing Systems

A-31

Automation System S7-400 Hardware and Installation

A5E00850741-01

Suppression for DC-Operated Coils

DC-operated coils are interconnected to diodes or Zener diodes.

+

-

+

-

With diode

With Zener diode

Figure A-9

Suppression for DC-Operated Coils

Suppression with Diodes / Zener Diodes

Suppression with diodes or Zener diodes exhibits the following characteristics:
• Switching overvoltages can be avoided entirely. A Zener diode has a higher

turn-off voltage.

• High turn-off delay (6 to 9 times higher than without suppressor circuits)

The Zener diode switches off more quickly than a diode circuit.

Suppression with AC-Operated Coils

AC-operated coils are suppressed with varistors or RC elements.

With varistor

With RC element

~

~

~

~

Figure A-10 Suppression with AC-Operated Coils

Suppression with a varistor exhibits the following characteristics:

• The amplitude of the switching overvoltage is limited but not attenuated.

• The steepness of the surge voltage remains the same.

• Low turn-off delay.
Suppression with an RC element exhibits the following characteristics:
• The amplitude and steepness of the switching overvoltage are reduced.
• Low turn-off delay.