ADS Environmental Services ADS TRITON+ QR 775027 A3 User Manual
Page 211

6-24 ADS TRITON+ Manual
15 fps option for this parameter. If the location is downstream
from a pump station and displays rapid changes in velocity
from reading to reading, ADS also recommends changing the
Maximum Velocity setting from Auto to a setting slightly
above the maximum recorded velocity.
Transmit Frequency Select the frequency at which to
transmit the signal. ADS recommends leaving the default
setting (High) selected.
Gain This value represents the factor applied to raw velocity
(RAWVEL entity in Qstart) to determine average velocity and
to calculate quantity for the Flow 1(2) device. Qstart does not
apply Gain to the velocity readings reported in Diagnostics,
where the raw velocity readings are used for comparison
against the manual measurements.
Cross Check Gain Enter the value by which to multiply raw
velocity readings in the monitor to determine average velocity
for comparison purposes in the monitor.
Store Data Select this checkbox to ensure the monitor logs
the velocity data to memory. This option is selected by default.
Advanced Select this button to access the Advanced
Parameters dialog.
Advanced Parameters dialog