beautypg.com

ADS Environmental Services ADS TRITON+ QR 775027 A3 User Manual

Page 204

background image

Configuration and Activation 6-17

Electronic Offset Enter the difference that exists between
the depth sensor readings and the manually measured depth.
The default value is 0.

Deadband Select the distance from the sensor face within
which readings received will be ignored. The default value
(Auto) represents a percentage of the flow depth and should be
sufficient under normal circumstances. It also is the best option
for handling shallow flows. However, consider another value
when the sensor readings reveal a potential problem with false
drop-outs. Choose a value for the deadband that is sufficiently
below the minimum depths that legitimately occur at the
monitoring point, yet above the confirmed drop-outs that have
been detected.

Store Data Select this checkbox to ensure the monitor logs
the depth data to memory. This option is selected by default.

Advanced Select this button to access the Advanced
Parameters
dialog.

Advanced Parameters dialog

Note: Modifications made to the Advanced Parameters
should be performed only by or under the guidance of
trained ADS personnel. Therefore, ADS recommends
leaving the default settings (Auto) in place.