Chapter 6 - Parameter description [FU1]
6-12
FU1-12: Starting DC Injection Braking Time
FU1-13: Staring DC Injection Braking Time
Inverter holds the starting frequency for Starting DC
Injection Braking Time. It outputs DC voltage to the motor
for FU1-13 [Starting DC Injection Braking Time] with the
FU1-12 [Starting DC Injection Braking Voltage] before
accelerating.
[Starting DC Injection Braking Operation]
☞
Note: The DC injection braking function does not function
when either FU1-12 or FU1-13 is set to “0”.
☞
Note: FU1-12 [Starting DC Injection Braking Voltage] is
also used as the DC Injection Braking Voltage for the
multifunction input when the multifunction input is set to “DC
braking”.
FU1-14: Pre-excitation Time
To set the time for pre-exitation (Flux gain time) before
starting Vector or Sensorless Vector control
After FU1-14 [Pre-excitation Time] elapses the motor
starts acceleration,
Code
LCD display
Factory setting
Setting range
FU1-14
PreExTime
1 [sec]
0 ~ 60 [sec]
FU1
► DcSt value
12 50 %
50
12
Factory Default:
50 %
50
FU1
► DcSt time
13 0.0 sec
0.0
13
Factory Default:
0.0 sec
0.0
Output Frequency
Time
FX-CM
ON
Output Voltage
Time
Time
Run Command
FU1-22
FU1-12
t1
t1: FU1-13 [Starting DC Injection
Braking Time]
Output Current
Time
Related Functions: FU2-33 [Rated Current of Motor]
FU2-33: the DC current is limited by this parameter.
FX-CM
Output freq
[ Hz ]
Output
voltage
[V]
T1 = Pre-excitation time
Ralated function : FU2-34 [No Load Motor Current (RMS)]
FU1-16 [Pre-excitation Current]
FU1
► PreExTime
14 1.0 sec
1.0
14
Factory Default:
1.0 sec
1.0