4 input/output group [i/o – HP 30 HP30 User Manual
Page 70
Chapter 5 - Parameter List
5-10
Keypad Display
Setting Range
Code
Description
LCD
7-Segment
LCD
7-Segment
Units
Factory
Default
Adj.
During
Run
Page
FU2-94
Parameter Write
Protection
Para. Lock
94
0 to 255
1
0
Yes
6-2
FU2-99 Return Code
Not
displayed
99
Not available
[PROG/ENT]
or
[SHIFT/ESC]
- 1 Yes
6-2
5.4 Input/Output Group [I/O]
Keypad Display
Setting Range
Code
Description
LCD
7-Segment
LCD
7-Segment
Units
Factory
Default
Adj.
During
Run
Page
I/O-00 Jump to Desired Code #
Jump code
Not displayed
1 to 84
Not available
1
1
Yes
6-2
I/O-01
Filtering Time Constant for
V1 Signal Input
V1 filter
01
0 to 10000 [ms]
1
10 [ms]
Yes
I/O-02 V1 Input Minimum Voltage
V1 volt x1
02
0 to 10 [V]
0.01
0.00 [V]
Yes
I/O-03
Frequency Corresponding
to V1 Input Minimum
Voltage
V1 freq y1
03
0 to FU1-20
0.01
0.00 {Hz}
Yes
I/O-04 V1 Input Maximum Voltage
V1 volt x2
04
0 to 10 [V]
0.01
10.00 [V]
Yes
I/O-05
Frequency Corresponding
to V1 Input Maximum
Voltage
V1 freq y2
05
0 to FU1-20
0.01 60.00 [Hz] Yes
6-2
I/O-06
Filtering Time Constant for
I Signal Input
I filter
06
0 to 10000 [ms]
1
10 [ms]
Yes
I/O-07 I Input Minimum Current
I curr x1
07
0 to 20 [mA]
0.01 4.00 [mA]
Yes
I/O-08
Frequency Corresponding
to I Input Minimum Current
I freq y1
08
0 to FU1-20
0.01
0.00 [Hz]
Yes
6-2
I/O-09 I Input Maximum Current
I curr x2
09
0 to 20 [mA]
0.01 20.00 [mA] Yes
I/O-10
Frequency Corresponding
to I Input Maximum
Current
I freq y2
10
0 to FU1-20
0.01 60.00 [Hz] Yes
6-2
None 0
half x1
1
I/O-11
Criteria for Analog Input
Signal Loss
Wire broken
11
below x1
2
- None Yes
6-2
Speed-L 0
Speed-M 1
Speed-H 2
XCEL-L 3
XCEL-M 4
XCEL-H 5
Dc-brake 6
2nd Func
7
Exchange 8
I/O-12 Multi-Function Input
Terminal ‘P1’ Define
P1 define
12
- Reserved -
9
- Speed-L Yes
6-2