Chapter 6 - Parameter Description [EXT]

6-55




EXT-12: Usage of Pulse Input Signal – Sub-B






This function is to select the usage of encoder pulse signal
of ‘Sub-B’ board. The pulse signal from encoder can be
used as the motor speed feedback or frequency reference.
When ‘Sub-B’ board is installed, FU2-40 must be set to
‘V/F’.

[None]
The encoder pulse signal is not used.

[Feed-back]
The encoder pulse signal is used as the motor speed
feedback. The inverter can maintain the motor speed
constantly, regardless of the load fluctuation, by using the
encoder feedback. The encoder pulse related functions
must be set correctly for better performance in EXT-15 ~
EXT-24.






[Reference]
The encoder pulse signal is used as the frequency
reference. When this function is selected, the frequency
reference selected in DRV-04 is ignored. Reference
Frequency versus Pulse Input Curve can be made by four
parameters of EXT-18 ~ EXT-20.










[Reference Frequency vs. Pulse Input]








EXT-13: Real Motor Speed Direction





If EXT-12 is set to 1 Feed-back with SUB-B mounted,
motor rotation direction is displayed in this parameter.

EXT-14: Encoder Feedback Frequency





Read frequency regardless of control mode if SUB-B is
installed with EXT-12 set to Feed-back.

EXT-15: Pulse Input Signal Selection – Sub-B






This code sets the encoder pulse to use. [A+B] uses two

encoder signal lines of A and B, and [A] uses one encoder

signal line of A or B.

–[A+B] is used when encoder and mot

or rotation direction is opposite

.

Related Functions: DRV-04 [Frequency Mode]

I/O-01 ~ I/O-05 [V1 Adjustment]

EXT

► F mode

14 None

0

14

Factory Default:

None

0

Related Functions: EXT-15 [Pulse Input Signal selection]

EXT-16 [Encoder Pulse Number]

EXT-22 [P-Gain for ‘Sub-B’]

EXT-23 [I-Gain for ‘Sub-B’]

EXT-24 [Slip Frequency for ‘Sub-B’]

Reference Frequency

EXT-21

Pulse Input
(0 to 10 kHz)

EXT-19

EXT-18

EXT-20

EXT

► F pulse set

15 A + B

0

15

Factory Default:

A + B

0

EXT

► RealSpdDir

13 None

0

13

Factory Default:

None

0

Related Functions: EXT-15 [Pulse Input Signal selection]

EXT-17 [Filtering Time Constant]

EXT-18 [Minimum Pulse Frequency]

EXT-19 [Minimum Output Frequency]

EXT-20 [Maximum Pulse Frequency]

EXT-21 [Maximum Output Frequency]

EXT

► ENC FeedBack

14 None

0

14

Factory Default:

None

0