Chapter 6 - Parameter Description [FU2]
6-24
FU2-40 ~ 44 [ Auto tuning ]
Note) * These values are automatically entered according to the
FU2-30 [Rated motor selection]. The above values are displayed
when FU2-30 is set to 5 (7.5 kW).
The auto tuning function automatically measures the
motor parameters needed for control selected in FU2-
39[Control mode selection] such as stator resistance,
rotor resistance, leakage inductance, no-load current
and Encoder feedback frequency. The motor does
not rotate during auto tuning so there is no need to
separate the motor from the system.
Encoder operating status can be checked.
The rated current, voltage, efficiency and slip
described in the motor nameplate should be entered
before performing auto tuning. If efficiency is not
indicated on the nameplate, use the preset value.
All or selected parameters can be tuned in Auto-
tuning mode.
[Motor rotation mode when set to All, Enc Test, Tr]
1. With PG Option installed: if FU2-40 is set to All, Stator
resistance (Rs), Leakage inductance (Lsigma),
Stator inductance (Ls), No-load current (Noload-
Curr), Speed Encoder status and Rotor constants
(Tr) are calculated.
2. Without PG Option installed: if FU2-40 is set to All,
Stator resistance (Rs), Leakage inductance
(Lsigma), Stator inductance (Ls) and No-load
current (Noload-Curr) are calculated.
3. if FU2-40 is set to Rs + Lsigma, Stator resistance
(Rs), Leakage inductance (Lsigma) are calculated.
4. Either PG Status or Rotor constant (Tr) can be
checked with PG option card installed.
[Motor non-rotation mode when set to Rs + Lsigma]
1. Stator resistance (Rs), Leakage inductance
(Lsigma) can be calculated by setting FU2-40 to
Rs + Lsigma.
2. User should set Stator resistance (Rs), No-load
current (Noload-Curr) and Rotor constants (Tr).
3. To automatically calculate the Stator inductance
(Ls), No-load current (Noload-Curr) and Rotor
constants (Tr), set the motor rotation mode and
FU2-40 to All.
[With PG option card installed]
1. Set EXT-12 to Feed-back.
2. Set EXT-15 to (A + B).
3. if FU2-40 is set to All, Stator resistance (Rs),
Leakage inductance (Lsigma), Stator inductance
(Ls), No-load current (Noload-Curr), and Rotor
constants (Tr) are calculated.
4. Stator resistance (Rs), Leakage inductance
(Lsigma) can be calculated by setting FU2-40 to
Rs + Lsigma.
5. User should set the Stator inductance (Ls), No-
load current (Noload-Curr) and Rotor constants
(Tr) if FU2-40 is set to Rs + Lsigma.
[Without PG option card installed]
1. if FU2-40 is set to All, Stator resistance (Rs),
Leakage inductance (Lsigma), Stator inductance
(Ls), No-load current (Noload-Curr) are
calculated.
2. If FU2-40 is set to Rs + Lsigma, Stator resistance
(Rs), Leakage inductance (Lsigma) is calculated.
3. User should set the Stator inductance (Ls), No-
load current (Noload-Curr).
FU2
► Auto tuning
40 --- NO ---
0
40
Factory Default:
NO
0
FU2
► Rs
*
41 0.171 ohm
0.171
41
Factory Default:
0.171 ohm
0.171
FU2
► Ls
*
43 29.03 mH
29.03
43
Factory Default:
29.03 mH
29.03
FU2
► Tr
*
44 260 ms
260
44
Factory Default:
260 ms
260
FU2
► Lsigma
*
42 3.34 mH
3.34
42
Factory Default:
3.34 mH
3.34