iii
Jog
Jog Operation
Auto Operation
Operates via Internal Sequence by Setting Multi-Function Terminal (5 Way * 8 Step)
Fault Reset
Trip Status is Removed when Protection Function is Activated
Operating Status
Frequency Detection Level, Overload Alarm, Stalling, Over Voltage, Under Voltage, Inverter
Overheating, Running, Stop, Constant Speed, Inverter By-Pass, Speed Searching, Auto-Operation
Step, Auto-Operation Sequence
Fault Output
Contact Output (30A, 30C, 30B) – AC 250V 1A, DC 30V 1A
Output S
ig.
Indicator(FM,LM)
Choose 1 from Output Frequency, Output Current, Output Voltage, DC Voltage, Output Torque
Output Voltage: 0 ~ 10V (for FM: Linear output, 15V Max., LM), Pulse output: 500Hz (for LM).
Operation Function
DC Braking, Frequency Limit, Frequency Jump, Second Function, Slip Compensation, Reverse
Rotation Prevention, Auto Restart, Inverter By-Pass, Auto-Tuning, PID Control
Inverter Trip
Over Voltage, Under Voltage, Over Current, Fuse Open, Ground Fault, Inverter Overheating, Motor
Overheating, Output Phase Open,
Overload Protection, External Fault 1, 2, Communication Error, Loss of Speed Command, Hardware
Fault, Option Fault etc.
Inverter Alarm
Stall Prevention, Overload Alarm, Temperature Sensor Fault
Pr
otective Function
Momentary Power Loss
Less than 15msec: Continuous Operation,
More than 15msec: Auto Restart Possible
Operation
Information
Output Frequency, Output Current, Output Voltage, Frequency Value Setting, Operating Speed, DC
Voltage, Output Torque
Display
Keypad
Trip
Information
Indicates a Fault when the Protection Function activates, Retains Up to 5 Faults
Ambient Temperature
-10 °C ~ 40 °C (14 °F ~ 104 °F), CE Certification: 41 °F ~ 104 °F (5 °C ~ 40 °C)
Storage Temperature
-20 °C ~ 65 °C (-4 °F ~ 149 °F)
Ambient Humidity
Less Than 90 % RH Max. (Non-Condensing), CE Certification: 5 ~85% (Non-Condensing)
Altitude - Vibration
Below 1,000m or 3,300ft above sea level · Below 5.9m/sec
2
(=0.6g)
Air Pressure
86 ~ 106kPa
En
vironment
Application Site
No Corrosive Gas, Combustible Gas, Oil Mist, or Dust
Cooling Method
Forced Air Cooling