beautypg.com

HP 30 HP30 User Manual

Page 123

background image

Chapter 6 - Parameter Description [FU2]

6-31

4

DRV-04 [Frequency Mode]

5

DRV-05 [Step Frequency 1]

6

DRV-06 [Step Frequency 2]

7

DRV-07 [Step Frequency 3]

8 DRV-08

[Output

Current]

9

DRV-09 [Motor Speed]

10

DRV-10 [DC link Voltage

11

DRV-11 [User Display selected in FU2-73]

12

DRV-12 [Fault Display]



FU2-73: User display selection

Related parameter : DRV-11 [User display selection]

Select the display as shown below in FU2-73 [User

display selection].

Setting FU2-73

Name

Description

0

Voltag

e

Output

voltage

Display output voltage of the
inverter (Factory setting)

1 Watt

Output

power

Display output power of the
inverter

Note) The display of “Watt” is approximate value.


FU2-74: Gain for Motor Speed Display






This code is used to change the motor speed display to
rotating speed (r/min) or mechanical speed (m/min). The
display is calculated by following equation.

Rotating speed = 120 x F / P, where F=Output frequency,
P= motor pole number

Mechanical speed = Rotating speed x Motor RPM Display
Gain





FU2-75: DB (Dynamic Braking) Resistor Mode
Selection






This code is used to protect the DB resistor from over
heating.

Setting Range

LCD 7-Seg

Description

None

0

This is selected when there is no resistor
connected. At this time, inverter does not
generate DB turn on signal.

Int. DB-R

1

This is selected when using the internal
DB resistor. This must be selected for
1~5 HP inverters because they have

internal DB resistor as a default.
Enable Duty (%): 2 ~ 3 %

Continuous Turn On Time: 5 seconds

Ext. DB-R

2

This is selected when using an external
DB resistor. This must be selected for

7.5~10 HP inverters. This must be
selected for 1~5 HP inverters in case of

using an external DB resistor.
Enable Duty (%): 0 ~ 30 %
Continuous Turn On Time: 15 seconds

The inverter turns the DB turn on signal OFF when the

Continuous Turn On Time expires during dynamic braking,
and an over voltage fault can occur. When this happens,
increase the deceleration time or install an external high-
duty DB resistor.

Install an exterior high-duty DB resistor when the load

accelerates and decelerates frequently. Set the FU2-75 [DB
Resistor Mode selection] to ‘Ext. DB-R’, and set the FU2-76
[Duty of DB Resistor].

This does not apply to 15~30 HP inverters. They need the

Optional DB unit to use DB resistor.

FU2-76: Duty of DB (Dynamic Braking) Resistor






This must be set when using an external DB resistor. The

FU2

► RPM factor

74 100 %

100

74

Factory Default:

100 %

100

FU2

► DB mode

75 Int. DB-R

1

75

Factory Default:

Int. DB-R

1

Related Functions: DRV-00 [Output Frequency]

DRV-09 [Motor Speed]

FU2-31 [Number of Motor Pole]

FU2

► DB %ED

76 10 %

10

76

Factory Default:

10 %

10