beautypg.com

HP 30 HP30 User Manual

Page 49

background image

Chapter 4 – Function Settings

4-3

FU2-40

Description

No

Motor constants calculation disabled

All

All constants can be measured in this code but different constants are tuned
according to control mode type;
For V/F, Slip compen , Sensorless_S, Sensorless_T:
(No-load current, stator resistance, leakage inductance, stator inductance
available)
Note) Only no-load current can be calculated during V/F and Slip compensation.
For Vector_SPD, Vector_T:
No-load current, stator resistance, leakage inductance, stator inductance,
encoder test, rotor filter time constant

Rs+Lsigma

Calculate stator resistance, leakage inductance

Enc Test

Calculate the encoder status

Tr

Calculate Rotor filter time constant


6) Sensorless vector control
Set FU2-39 to 2 {Sensorless_S} or 3 {Sensorless_T} to enable Sensorless vector control. It is strongly recommended to
perform Auto-tuning for Sensorless before starting Sensorless control in order to maximize performance. Two types of
Sensorless vector control are available; Sensorless_S or Sensorless_T.

Parameter Name

Code

Description

Control mode selection

FU2-39

Select Sensorless_S or Sensorless_T

P, I gain for sensorless

control

FU2-45, FU2-46 Setting gain for Sensorless_S control

Starting freq

FU1-22

Starting freq of the motor

7) Vector control
Set FU2-39 to 4 {Vector_SPD} or 5{Vector_TRQ} to enable Vector control. Encoder should be installed to the motor with
Sub-B or Sub-D boards in the inverter to start this control.

Parameter Name

Code

Description

Usage of Pulse Input

Signal

EXT-12

Defines the method of pulse input with SUB-B or SUB-D
boards mounted. Vector control setting is valid only after
this parameter is set to 1 {Feed-back}.

Pulse Input Signal

Selection

EXT-15

3 types of pulse input : (A+B), A, -(A+B)

Encoder Pulse Number

EXT-16

Enter the pulse number of encoder in the motor.