beautypg.com

HP 30 HP30 User Manual

Page 128

background image

Chapter 6 - Parameter Description [I/O]

6-36

This is the filtering time constant for ‘I’ signal input. If the ‘I’
signal is affected by noise causing unstable operation of
the inverter, increase this value. Increasing this value
makes response time slower.





This is the minimum current of the ‘I’ input at which inverter
outputs minimum frequency.





This is the inverter output minimum frequency when there
is minimum current (I/O-07) on the ‘I’ terminal.





This is the maximum current of the ‘I’ input at which
inverter outputs maximum frequency.





This is the inverter output maximum frequency when there
is the maximum current (I/O-09) on the ‘I’ terminal.











[Reference Frequency vs. Analog Current Input, I (4 to 20mA)]





I/O-11: Criteria for Analog Input Signal Loss






This is to set the criteria for analog input signal loss when
DRV-04 [Frequency Mode] is set to ‘V1’, ‘I’ or ‘V1+I’.
Following table shows the setting value.

Setting Range

LCD 7-Seg

Description

None

0

Does not check the analog input
signal.

half of x1

1

The inverter determines that the
frequency reference is lost when the
analog input signal is less than half of

the minimum value (I/O-02 or I/O-07).

below x1

2

The inverter determines that the
frequency reference is lost when the

analog input signal is less than the
minimum value (I/O-02 or I/O-07).


When the analog input signal is lost, inverter displays the
following table.

Setting Range
LCD 7-Seg

Description

LOP

LP

Loss of frequency reference from Option
Board (DPRAM time out)

LOR

LR

Loss of frequency reference from Option
Board (Communication fault)

LOV

LV

Loss of analog input signal, V1

LOI

LI

Loss of analog input signal, I

LOX

LX

Loss of frequency reference from Sub-
Board, V2 or ENC


Related Functions: I/O-48 [Lost command] selects the
operation after determining the loss of frequency reference.






I/O

► I curr x1

07 4.00 mA

4.00

07

Factory Default:

4.00 mA

4.00

I/O

► I freq y1

08 0.00 Hz

0.00

08

Factory Default:

0.00 Hz

0.00

I/O

► I curr x2

09 20.00 mA

Factory Default:

20.00 mA

20.00

I/O

► I freq y2

10 60.00 Hz

60.00

10

Factory Default:

60.00 Hz

60.00

Reference Frequency

I/O-10

Analog Voltage
Input (V1)

I/O-08

I/O-07 I/O-09

Related Functions: DRV-04 [Frequency Mode]

FU1-20 [Maximum Frequency]

I/O

► Wire broken

11 None

0

11

Factory Default:

None

0

20.00

09