HP 30 HP30 User Manual
Page 157
Chapter 6 - Parameter Description [APP]
6-65
When the Flo
increse
When the Flo
decrese
Start
Stop
Aux. Motor
Start/Stop
Frequency rise according to
APP-19
Output
Frequency
Aux start DT(APP-19)
Stop freq
1(APP-15)
Starting
Freq.
Aux stop DT(APP-20)
Frequency drop according to
APP-20
Flow
Start freq 1
(APP-11)
The inverter turns on AUX, RLY1, RLY2, and RLY3 in
order if the output frequency is over the frequencies set in
APP-11 to APP-14, respectively, and the time is over APP-
19.
APP-15: Stop Frequency of Aux. Motor 1
APP-16: Stop Frequency of Aux. Motor 2
APP-17: Stop Frequency of Aux. Motor 3
APP-18: Stop Frequency of Aux. Motor 4
The inverter turns off RLY3, RLY2, RLY1, and AUX in
order if the output frequency is below the frequencies set
in APP-15 to APP-18, respectively, and the time is over
APP-20.
APP-19: Delay Time before Operating Aux. Motor
APP-20: Delay Time before Stopping Aux. Motor
Sets the time the inverter waits before starting the auxiliary
motors.
Sets the time the inverter waits before stopping the
auxiliary motors.
[Aux. Motor Start/Stop with MMC]
APP-21: The Number of Aux. Motors
Sets the number of auxiliary motors connected to the
inverter.
APP
►Start freq3
13 49.99 Hz
49.99
13
Factory Default: 49.99
Hz
49.99
APP
►Start freq4
14 49.99 Hz
49.99
14
Factory Default: 49.99
Hz
49.99
APP
►Stop freq1
15 15.00 Hz
15.00
15
Factory Default: 15.00
Hz
15.00
APP
►Stop freq2
16 15.00 Hz
15.00
16
Factory Default: 15.00
Hz
15.00
APP
►Stop freq3
17 15.00 Hz
15.00
17
Factory Default: 15.00
Hz
15.00
APP
►Stop freq4
18 15.00 Hz
15.00
18
Factory Default: 15.00
Hz
15.00
APP
►Aux Start DT
19 60.0 sec
60.0
19
Factory Default: 60.0
sec
60.0
APP
►Aux Stop DT
20 60.0 sec
60.0
20
Factory Default: 60.0
sec
60.0
APP
►Nbr Aux’s
21 4
4
21
Factory Default: 4
4