beautypg.com

HP 30 HP30 User Manual

Page 157

background image

Chapter 6 - Parameter Description [APP]

6-65

When the Flo
increse
When the Flo
decrese

Start

Stop

Aux. Motor
Start/Stop

Frequency rise according to
APP-19

Output
Frequency

Aux start DT(APP-19)

Stop freq

1(APP-15)

Starting

Freq.

Aux stop DT(APP-20)

Frequency drop according to
APP-20

Flow

Start freq 1

(APP-11)











The inverter turns on AUX, RLY1, RLY2, and RLY3 in
order if the output frequency is over the frequencies set in
APP-11 to APP-14, respectively, and the time is over APP-
19.

APP-15: Stop Frequency of Aux. Motor 1
APP-16: Stop Frequency of Aux. Motor 2
APP-17: Stop Frequency of Aux. Motor 3
APP-18: Stop Frequency of Aux. Motor 4





















The inverter turns off RLY3, RLY2, RLY1, and AUX in
order if the output frequency is below the frequencies set
in APP-15 to APP-18, respectively, and the time is over
APP-20.


APP-19: Delay Time before Operating Aux. Motor
APP-20: Delay Time before Stopping Aux. Motor






Sets the time the inverter waits before starting the auxiliary
motors.





Sets the time the inverter waits before stopping the
auxiliary motors.















[Aux. Motor Start/Stop with MMC]


APP-21: The Number of Aux. Motors






Sets the number of auxiliary motors connected to the
inverter.


APP

►Start freq3

13 49.99 Hz

49.99

13

Factory Default: 49.99

Hz

49.99

APP

►Start freq4

14 49.99 Hz

49.99

14

Factory Default: 49.99

Hz

49.99

APP

►Stop freq1

15 15.00 Hz

15.00

15

Factory Default: 15.00

Hz

15.00

APP

►Stop freq2

16 15.00 Hz

15.00

16

Factory Default: 15.00

Hz

15.00

APP

►Stop freq3

17 15.00 Hz

15.00

17

Factory Default: 15.00

Hz

15.00

APP

►Stop freq4

18 15.00 Hz

15.00

18

Factory Default: 15.00

Hz

15.00

APP

►Aux Start DT

19 60.0 sec

60.0

19

Factory Default: 60.0

sec

60.0

APP

►Aux Stop DT

20 60.0 sec

60.0

20

Factory Default: 60.0

sec

60.0

APP

►Nbr Aux’s

21 4

4

21

Factory Default: 4

4