HP 30 HP30 User Manual
Page 68
Chapter 5 - Parameter List
5-8
Keypad Display
Setting Range
Code
Description
LCD
7-Segment
LCD
7-Segment
Units
Factory
Default
Adj.
During
Run
Page
FU2-43
Stator Inductance of
Motor
Ls
43
0 to (depending on FU2-30) [mH]
No
FU2-44 Rotor Time Constant
Tr
44
0 to (depending on FU2-30) [mH]
No
FU2-45
P Gain for Sensorless
Control
SL P-gain
45
0 to 32767
1
1000
Yes
FU2-46
I Gain for Sensorless
Control
SL I-gain
46
0 to 32767
1
100
Yes
6-2
No 0
FU2-47 PID Operation Selection proc PI mode
47
Yes 1
- No No
6-2
Ramp freq.
0
FU2-48
22
PID Reference
Frequency Selection
PID Ref
48
Target freq.
1
- Ramp
freq. No 6-2
Freq mode
0
Keypad-1 1
Keypad-2 2
V1 3
I 4
FU2-49
PID Reference Mode
Selection
PID Ref Mode
49
V2 5
- Freq
mode No 6-2
Ramp freq.
0
FU2-50
PID Output Direction
Selection
PID Out Dir
50
Target freq.
1
- Ramp
freq. No 6-2
I 0
V1 1
FU2-51
PID Feedback Signal
Selection
PID F/B
51
V2 2
- I No
FU2-52 P Gain for PID Control
PID P-gain
52
0 to 999.9 [%]
0.1
100.0 [%]
Yes
FU2-53 I Gain for PID Control
PID I-time
53
0 to 32.0 [sec]
0.1
30.0 [sec]
Yes
FU2-54 D Gain for PID Control
PID D-time
54
0 to 999.9 [msec]
0.1
0.0 [msec] Yes
FU2-55
High Limit Frequency for
PID Control
PID +limit
55
0 to 99.99 [Hz]
0.01 60.00 [Hz] Yes
FU2-56
Low Limit Frequency for
PID Control
PID -limit
56
0 to 99.99 [Hz]
0.01 60.00 [Hz] Yes
6-2
No 0
FU2-57 PID Output Inversion
PID Out Inv.
57
Yes 1
- No No
FU2-58 PID Output Scale
PID OutScale
58
0 to 999.9 [%]
0.1
100 [%]
No
FU2-59 PID P2 Gain
PID P2-gain
59
0 to 100 [%]
0.1
100 [%]
No
FU2-60 P Gain Scale
P-gain Scale
60
0 to 100 [%]
0.1
100 [%]
No
6-2
FU2-69
Accel/Decel Change
Frequency
Acc/Dec ch F
69
0 to FU1-20
No
6-2
Max freq
0
FU2-70
Reference Frequency for
Accel and Decel
Acc/Dec freq
70
Delta freq
1
- Max
freq No 6-2
0.01 [sec]
0
0.1 [sec]
1
FU2-71 Accel/Decel Time Scale
Time scale
71
1 [sec]
2
0.01 0.1
[sec] Yes 6-2
22
Code FU2-48 through FU2-60 appears only when FU2-47 is set to ‘Yes’.