Chapter 5 - Parameter List

5-8

Keypad Display

Setting Range

Code

Description

LCD

7-Segment

LCD

7-Segment

Units

Factory

Default

Adj.

During

Run

Page

FU2-43

Stator Inductance of
Motor

Ls

43

0 to (depending on FU2-30) [mH]

No

FU2-44 Rotor Time Constant

Tr

44

0 to (depending on FU2-30) [mH]

No

FU2-45

P Gain for Sensorless
Control

SL P-gain

45

0 to 32767

1

1000

Yes

FU2-46

I Gain for Sensorless
Control

SL I-gain

46

0 to 32767

1

100

Yes

6-2

No 0

FU2-47 PID Operation Selection proc PI mode

47

Yes 1

- No No

6-2

Ramp freq.

0

FU2-48

22

PID Reference
Frequency Selection

PID Ref

48

Target freq.

1

- Ramp

freq. No 6-2

Freq mode

0

Keypad-1 1
Keypad-2 2

V1 3

I 4

FU2-49

PID Reference Mode
Selection

PID Ref Mode

49

V2 5

- Freq

mode No 6-2

Ramp freq.

0

FU2-50

PID Output Direction
Selection

PID Out Dir

50

Target freq.

1

- Ramp

freq. No 6-2

I 0

V1 1

FU2-51

PID Feedback Signal
Selection

PID F/B

51

V2 2

- I No

FU2-52 P Gain for PID Control

PID P-gain

52

0 to 999.9 [%]

0.1

100.0 [%]

Yes

FU2-53 I Gain for PID Control

PID I-time

53

0 to 32.0 [sec]

0.1

30.0 [sec]

Yes

FU2-54 D Gain for PID Control

PID D-time

54

0 to 999.9 [msec]

0.1

0.0 [msec] Yes

FU2-55

High Limit Frequency for
PID Control

PID +limit

55

0 to 99.99 [Hz]

0.01 60.00 [Hz] Yes

FU2-56

Low Limit Frequency for
PID Control

PID -limit

56

0 to 99.99 [Hz]

0.01 60.00 [Hz] Yes

6-2

No 0

FU2-57 PID Output Inversion

PID Out Inv.

57

Yes 1

- No No

FU2-58 PID Output Scale

PID OutScale

58

0 to 999.9 [%]

0.1

100 [%]

No

FU2-59 PID P2 Gain

PID P2-gain

59

0 to 100 [%]

0.1

100 [%]

No

FU2-60 P Gain Scale

P-gain Scale

60

0 to 100 [%]

0.1

100 [%]

No

6-2

FU2-69

Accel/Decel Change
Frequency

Acc/Dec ch F

69

0 to FU1-20

No

6-2

Max freq

0

FU2-70

Reference Frequency for
Accel and Decel

Acc/Dec freq

70

Delta freq

1

- Max

freq No 6-2

0.01 [sec]

0

0.1 [sec]

1

FU2-71 Accel/Decel Time Scale

Time scale

71

1 [sec]

2

0.01 0.1

[sec] Yes 6-2

22

Code FU2-48 through FU2-60 appears only when FU2-47 is set to ‘Yes’.