Chapter 6 - Parameter Description [I/O]

6-43

I/O-21 ~ I/O-24: Step Frequency 4, 5, 6, 7










These codes set the step frequencies. These frequencies
are applied when the multi-function input terminals (P1, P2,
P3) select the step. See [Speed-L, Speed-M, Speed-H] in
I/O-12 ~ I/O-14.

























[‘JOG’ and ‘Multi-Step’ Operation]


I/O-25 ~ I/O-38: 1

st

~ 7

th

Accel/Decel Time










These codes are applied when the multi-function input
terminals (P1, P2, P3) select the Accel/Decel time. See
[XCEL-L, XCEL-M, XCEL-H] in I/O-12 ~ I/O-14.





I/O-40: FM (Frequency Meter) Output
I/O-41: FM Adjustment










Frequency meter displays the inverter output Frequency,
Current, Voltage and DC link voltage with pulse signals on
the FM terminal. The average ranges from 0V to 10V. I/O-
41 is used to adjust the FM value.

[Frequency]
FM terminal outputs inverter output frequency. The output
value is determined by,
FM Output Voltage = (Output freq. / Max. freq.) × 10V ×
IO-41 / 100

I/O

► Step freq-4

21 40.00 Hz

40.00

21

Factory Default:

40.00 Hz

40.00

I/O

► Step freq-7

24 30.00 Hz

30.00

24

Factory Default:

30.00 Hz

30.00

Related Functions: DRV-05 ~ DRV-07 [Step Frequency 1 ~ 3]

I/O-12 ~ I/O-14 [Multi-function inputs]

I/O-17 [Filtering Time Constant]

I/O

► Acc time-1

25 20.0 sec

20.00

25

Factory Default:

20.0 sec

20.0

I/O

► Dec time-7

38 20.0 sec

20

38

Factory Default:

20.0 sec

20.0

Related Functions: DRV-01 ~ DRV-02 [Accel/Decel Time]

FU2-70 [Reference Freq. for Accel/Decel]

FU2-71 [Accel/Decel Time Scale]

I/O-12 ~ I/O-14 [Multi-function inputs]

I/O

► FM mode

40 Frequency

0

40

Factory Default:

Frequency

0

I/O

► FM Adjust

41 100 %

100

41

Factory Default:

100 %

100

P1-CM

ON

Output Frequency

Time

Time

P2-CM

Time

P3-CM

Time

Speed 1

JOG-CM

Time

FX-CM

Time

RX-CM

Time

ON

ON

ON

ON

ON

ON

ON

ON

ON

Speed 0

Speed 2

Speed 3

Speed 4

Speed 5

Speed 6
Speed 7

JOG