HP 30 HP30 User Manual
Page 125
Chapter 6 - Parameter Description [FU2]
6-33
FU2-93: Parameter Initialize
This is used to initialize parameters back to the factory
default values. Each parameter group can be initialized
separately.
Setting Range
LCD 7-Seg
Description
No
0
Displayed after initializing
parameters.
All Groups
1
All parameter groups are initialized to
factory default value.
DRV
2
Only Drive group is initialized.
FU1
3
Only Function 1 group is initialized.
FU2
4
Only Function 2 group is initialized.
I/O
5
Only Input/Output group is initialized.
EXT
6
Only External group is initialized.
COM
7
Only Communication group is
initialized.
APP
8
Only Application group is initialized.
☞
Note: FU1-30 ~ FU1-37 [Motor Parameters] must be set
first after initializing parameters.
FU2-94: Parameter Write Protection
This function is used to lock the parameters from being
changed. When the parameters are locked, the display
arrow changes from solid to dashed line.
The lock and unlock code is ‘12’.
FU2-99: Return Code (7-Segment Keypad)
This code is used to exit a group when using a 7-segment
keypad. After pressing PROG/ENT key, set the value to ‘1’
and press the PROG/ENT key again to exit.
FU2
► Para. init
93 --- No ---
0
93
Factory Default: No
0
FU2
► Para. lock
94 0
0
94
Factory Default:
0
0
0
99
Factory Default:
0
Related Functions: FU1-99 [Return Code]
I/O-99 [Return Code]
EXT-99 [Return Code]
COM-99 [Return Code]