Chapter 7 - Options

7-31

7.6.4

Micro surge filter (Designed for Inverter-driven 400V Class motor)

In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor terminals.
Especially for a 400V class motor, the surge voltage may deteriorate the insulation. When the 400V class motor is
driven by the inverter, consider the following measures:
Measures

It is recommended to taking either of the following measures:

1) Rectifying the motor insulation

For the 400V class motor, use an insulation-rectified motor. Specifically,

1) Specify the “400V class inverter-driven, insulation-rectified motor”.
2) For the dedicated motor such as the constant-torque motor and low-vibration motor, use the “inverter-driven,

dedicated motor”.

2) Suppressing the surge voltage on the inverter output side

On the secondary side of the inverter, connect the optional surge voltage suppression filter.


Wiring

Caution

_

Check the Input/Output when wiring the filter.

_

Wiring distance from inverter output to filter input should not exceed 5 meter.

_

Wiring distance from filter to motor should not exceed 300 meter .

U,V,W


Inverter

Motor

5m

Within 5m

Within 300m

Surge

filter