Chapter 1 - installation, 008 sv ac 2 n u – HP 30 HP30 User Manual
Page 13
1-1
CHAPTER 1 -
INSTALLATION
1.1 Inspection
Inspect the inverter for any damage that may have occurred during shipping.
Check the nameplate on the inverter. Verify the inverter unit is the correct one for the application. The numbering
system for the inverter is as shown below.
CMC
Inverter
Motor Capacity Series Name
Input Voltage
008: 1 HP 185: 25 HP
2 : 200 ~ 230V (±
±
±
±
10%) 50/60Hz
015: 2 HP 220: 30 HP
4 : 380 ~ 460V (±
±
±
±
10%) 50/60Hz
UL Listed
022: 3 HP 300: 40 HP
(UL508C)
037: 5 HP 370: 50 HP
055: 7.5 HP 450: 60 HP
Without
075: 10 HP 550: 75 HP
Keypad
110: 15 HP 750: 100 HP
150: 20 HP
1.2 Environmental Conditions
Verify ambient condition for the mounting location.
- Ambient temperature should not be below 14ºF (-10ºC) or exceed 104ºF (40ºC).
- Relative humidity should be less than 90% (non-condensing).
- Altitude should be below 3,300ft (1,000m).
Do not mount the inverter in direct sunlight and isolate it from excessive vibration.
If the inverter is going to be installed in an environment with high probability of penetration of dust, it must be located
inside watertight electrical boxes, in order to get the suitable IP degree.
1.3 Mounting
The inverter must be mounted vertically with sufficient horizontal and vertical space between adjacent equipment
(A= Over 6" (150mm), B= Over 2" (50mm)).
008
SV
AC
2
N
U
A
B
A
B