Chapter 2 - Operation

2-10

2.4 Operation Method

The ACtionMaster has several operation methods as shown below.

Operation Method

Function

Function Setting

Operation using Keypad

Run/Stop command and frequency are set only through the
keypad.

DRV 03: Keypad
DRV 04: Keypad-1 or -2

Operation using
Control Terminals

Closing FX or RX terminal performs Run/Stop.
Frequency reference is set through V1 or I or V1+I terminal.

DRV 03: Fx/Rx-1 or -2
DRV 04: V1 or I or V1+I

Run/Stop is performed by the keypad.
Frequency reference is set through the V1 or I or V1+I
terminal.

DRV 03: Keypad-1 or -2
DRV 04: V1 or I or V1+I

Operation using both
Keypad and Control
Terminals

Closing FX or RX terminal performs Run/Stop.
Frequency reference is set through the keypad.

DRV 03: Fx/Rx-1 or -2
DRV 04: Keypad-1 or -2

Operation using
Option Boards

Operation using option board.
The ACtionMaster has five option boards and three sub-
boards.
Option Boards: RS485, Device-Net, F-Net, ProfiBus and
ModBus
Sub-Boards: Sub-A Board, Sub-B Board, Sub-C Board and
Sub-D Board.

Please refer to ‘Chapter 7 -
Options’ for more
information.