3 unit description, 1 technical data – KACO Powador XP100-HV User Manual
Page 8

Page 8
Operating Instructions Powador XP100-HV
U n i t D e s c r i p t i o n
3 Unit
Description
3.1 Technical
Data
Electrical Data
Input levels
Max. PV generator power
110 kW
MPPT range
450 to 830 V
No-load voltage
A maximum of 1000 V
Voltage/current ripple
< 3 % / < 4 %
Max. input current
245 A
Overvoltage protection
SPD
Output levels
Rated power
100 kW
Max. power
100 kW
Line voltage
In accordance with country-specifi c guidelines
Output voltage
3*380 / 400 V (±10%)
Rated current
153 A
Max. current
153 A
Rated frequency
50 / 60 Hz
cos phi
≥ 0.99 at rated power
Distortion factor
< 3 % at rated power
Fault signal relay
Potential-free NO contact, max. 30 V/1 A
S0 output
Open collector output, max. 30 V/50 mA
General electrical data
Max. effi
ciency
97.10 %
European effi
ciency
96.50 %
Standby
< 100 W
Grid monitoring
Compliant with VDEW guidelines
Table 1: Electrical data of the inverter